The line voltage and the phase voltage are two different ways of measuring voltage within a three-phase system.
In a three-phase distribution system with a neutral, we find five conductors:
- Three Phases (L1, L2, L3).
- One Neutral (N).
- One Ground (PE).
The voltage depends on the two points between which we define it.
Phase Voltage ( )
In a star-connected source, the phase voltage,
- Standard Value (Europe): 230 V.
- Usage: It is used to power single-phase loads: sockets, computers, lights, small relay coils.
Line Voltage ( )
The line voltage
- Standard Value (Europe): 400 V.
- Usage: It powers heavy loads: three-phase motors, welders, large furnaces.
The √3 Factor
Where does the 400 come from? If one phase has 230V and the other also has 230V… Shouldn’t the difference be 0V or 460V? No, because they are 120 degrees out of phase. They do not reach their peak simultaneously.
The geometric relationship between these two vectors forms a triangle that is resolved using the square root of 3.
If we do the calculation with the current European standard:
That is why we nominally state 400V.
In the past, Spain had 127V / 220V networks.
- Phase-Neutral: 127V (for lights).
- Phase-Phase: 220V (for power). Today the standard has risen to 230V / 400V to transport more power using the same cables.
Why does 400 V appear?
Many people think: “If L1 has 230V and L2 has 230V… the difference should be zero.” That would be true if they were identical voltages and in phase. But they are 120 degrees out of phase.
When subtracted as phasors, we obtain another sine wave whose RMS value is
Safety in Measurement
Both 230 V and 400 V can cause serious or fatal injuries. Do not open or measure a live panel unless you have the proper training, authorization, procedure, and equipment.
Never assume a cable is Neutral based on its color. Always measure. If you accidentally connect a 230V device (like your laptop) between two phases (400V), it will explode instantly.